Oil Check 500 Monitoring Systems
Compressed Air Quality
Unit of Measure
Items |
![]() 0500 5000 Intelligent Chart Recorder in Basic Version with 4 Sensor Input Web Price QUOTE
|
![]() 0699 0081 Intelligent Chart Recorder in Portable Version with 4 Sensor Input Web Price QUOTE
|
![]() 0699 3930 Replacement Oil Check 500 for The Period of Re-Calibration Web Price QUOTE
|
![]() 0699 8080 Pre-Calibrated Sensor Unit for The Oil Check 500 with Certificate Web Price QUOTE
|
![]() 0699 3405 Re-Calibration Oil Check 500 with Certificate Web Price QUOTE
|
|||||
Description |
N/A
NEW! Oil Check 500 - The monitoring system for permanent highly precise measurement of the vaporous residual oil content compressed air, nitrogen and gases "Forced Pressure Variation" for long-term stable measurement results - Auto-calibration Thanks to the innovative "Forced Pressure Variation" measuring method, the Oil Check 500 generates reference gas internally in different mass concentrations. With the help of this process, which is intellectually protected by CS INSTRUMENTS, components in the measurement signal caused by ageing or contamination, in particular long-term drifts, can be compensated. No wearing parts such as activated carbon filters are necessary for the generation of zero air. The result is a low-maintenance and long-term stable measurement |
N/A
NEW! Oil Check 500 - The monitoring system for permanent highly precise measurement of the vaporous residual oil content compressed air, nitrogen and gases "Forced Pressure Variation" for long-term stable measurement results - Auto-calibration Thanks to the innovative "Forced Pressure Variation" measuring method, the Oil Check 500 generates reference gas internally in different mass concentrations. With the help of this process, which is intellectually protected by CS INSTRUMENTS, components in the measurement signal caused by ageing or contamination, in particular long-term drifts, can be compensated. No wearing parts such as activated carbon filters are necessary for the generation of zero air. The result is a low-maintenance and long-term stable measurement |
N/A | N/A | N/A | |||||
Approve Payments |
N/A
Finance with Approve Payments |
|||||||||
Measured Medium |
N/A
Compressed air, nitrogen, (free from aggressive, corrosive, acid, toxic, flammable and oxidizing components). Further gases on request |
N/A
Compressed air, nitrogen, (free from aggressive, corrosive, acid, toxic, flammable and oxidizing components). Further gases on request |
N/A | N/A | N/A | |||||
Measuring Unit | N/A Residual oil content in mg oil/norm m³ referred to 14.5 psi [abs], +68 F, 0% relative humidity, in accordance with ISO 8573-1 | N/A Residual oil content in mg oil/norm m³ referred to 14.5 psi [abs], +68 F, 0% relative humidity, in accordance with ISO 8573-1 | N/A | N/A | N/A | |||||
Identifiable Substances | N/A Aromatic Hydrocarbons Functional Hydrocarbons Hydrocarbons | N/A Aromatic Hydrocarbons Functional Hydrocarbons Hydrocarbons | N/A | N/A | N/A | |||||
Field of Application | N/A After activated carbon filter, after activated carbon adsorber, after oil-free compressor, always with connected upstream filtration and dryer | N/A After activated carbon filter, after activated carbon adsorber, after oil-free compressor, always with connected upstream filtration and dryer | N/A | N/A | N/A | |||||
Ambient Temperature | N/A +68 to +113 ºF | N/A +68 to +113 ºF | N/A | N/A | N/A | |||||
Relative Humidity without Condensation | N/A ≤ 75 % | N/A ≤ 75 % | N/A | N/A | N/A | |||||
Compressed Air Temperature | N/A +68 to +113 ºF | N/A +68 to +113 ºF | N/A | N/A | N/A | |||||
Operational Overpressure1 | N/A 43.5 to 130.5 psi | N/A 43.5 to 130.5 psi | N/A | N/A | N/A | |||||
Humidity of Measured Gas | N/A ≤ 40% relative humidity, pressure dew point maximum +50 ºF, non-condensable humidity | N/A ≤ 40% relative humidity, pressure dew point maximum +50 ºF, non-condensable humidity | N/A | N/A | N/A | |||||
Compressed Air Connection | N/A G-1/4 in. Female Thread According to International Organization for Standardization (ISO) 228-1 | N/A G-1/4 in. Female Thread According to International Organization for Standardization (ISO) 228-1 | N/A | N/A | N/A | |||||
Measured Values | N/A mg/norm m³, pressure and temperature compensated residual oil vapor content | N/A mg/norm m³, pressure and temperature compensated residual oil vapor content | N/A | N/A | N/A | |||||
Measuring Range2 | N/A 0.001 to 5 mg/m³ | N/A 0.001 to 5 mg/m³ | N/A | N/A | N/A | |||||
Detection limit (Residual Oil) | N/A 0.001 mg/m³ | N/A 0.001 mg/m³ | N/A | N/A | N/A | |||||
Approximate Flow of Measuring Gas | N/A 0.042 ft³/min | N/A 0.042 ft³/min | N/A | N/A | N/A | |||||
Note for Approximate Flow of Measuring Gas | N/A Referred to to 14.5 psi [abs] and +68 F, (atmospheric conditions) | N/A Referred to to 14.5 psi [abs] and +68 F, (atmospheric conditions) | N/A | N/A | N/A | |||||
Alternating Current (AC) Voltage | N/A 100 to 240 V | N/A 100 to 240 V | N/A | N/A | N/A | |||||
Phase | N/A 1 | N/A 1 | N/A | N/A | N/A | |||||
Grounding | N/A Protective Earth (PE) | N/A Protective Earth (PE) | N/A | N/A | N/A | |||||
Frequency | N/A 50 to 60 Hz | N/A 50 to 60 Hz | N/A | N/A | N/A | |||||
Voltage Tolerance | N/A ±10 % | N/A ±10 % | N/A | N/A | N/A | |||||
Digital Output | N/A Ethernet Via DS 400/500 RS 485 Interface (Modbus-Remote Terminal Unit (RTU)) | N/A Ethernet Via DS 400/500 RS 485 Interface (Modbus-Remote Terminal Unit (RTU)) | N/A | N/A | N/A | |||||
Analog Output Current (Electrically Isolated) | N/A 4 to 20 mA | N/A 4 to 20 mA | N/A | N/A | N/A | |||||
Optional Output | N/A 2 x 4...20 mA analog output (electrically isolated), 2 alarm relays for external alarm unit, alarm values freely adjustable | N/A 2 x 4...20 mA analog output (electrically isolated), 2 alarm relays for external alarm unit, alarm values freely adjustable | N/A | N/A | N/A | |||||
Operating Hours Counter | N/A Integrated | N/A Integrated | N/A | N/A | N/A | |||||
Width | N/A 7.87 in | N/A 7.87 in | N/A | N/A | N/A | |||||
Height | N/A 5.12 in | N/A 5.12 in | N/A | N/A | N/A | |||||
Depth | N/A 4.72 in | N/A 4.72 in | N/A | N/A | N/A | |||||
Approximate Weight | N/A 15.4 lb | N/A 15.4 lb | N/A | N/A | N/A | |||||
Stationary Solution |
N/A
Item # - 0554 8040 Description - CS Basic - data evaluation in graphic and table form - readout of the measured data via USB or Ethernet. License for 2 working places Item # - 0699 0080 Description - Residual oil measurement: Oil Check 500 - residual oil measurement of the vaporous oil content from 0,001…5 mg/m³, 43.5 ... 130.5 psi. High-precision PID-Sensor, innovative ”Forced Pressure Variation“ measuring method, with integrated display, with 4...20 mA analog output and digital Modbus RTU interface, incl. calibration certificate Item # - Z699 0078 Description - Options: Integrated heating element for the stationary Oil Check 500. Keeps the gas temperature constantly above 68 ºF. Recommended for installations where the room temperature may fall below 68 ºF. Item # - Z699 0178 Description - 2x 4...20 mA analog output (electrically isolated) Item # - Z699 0175 Description - Sampling system Oil Check 500: Sampling system consisting of 1/2" ball valve (oil- and grease-free), 3.28 ft stainless steel tube 6x1 mm (oil- and grease-free), clamp screwing (oil- and grease-free) Item # - Z699 0174 Description - Alternative: Portable sampling system consisting of 6.56 ft PTFE hose, quick coupling (oil- and grease-free) Item # - Z699 0076 Description - Options for systems > 130.5 psi: Pressure reducer (oil- and grease-free), input pressure max. 4350 psi, output pressure up to 130.5 psi Item # - 0553 0104 Description - Connection cable for probes 16 ft with open ends Item # - 0699 0040 Description - PC 400 particle counter up to 0.1 ?m for compressed air and gases, incl. pressure reducer/sampling hose, calibration certificate, Modbus-RTU interface Item # - 0553 0104 Description - Connection cable for probes, 16 ft with open ends Item # - 0699 0510 Description - FA 510 dew point sensor for adsorption dryers -112 ... 68 Ftd incl. factory certificate, 4…20 mA analog output (3-wire connection) and Modbus-RTU interface Item # - 0699 3390 Description - Standard measuring chamber up to 232 psi Item # - 0553 0104 Description - Connection cable for VA/FA series, 16 ft with open ends Item # - Z699 0077 Description - External alarm unit, wired ready to plug in, for direct connection to the Oil Check 500 with 16 ft cable (buzzer and continuous red light) |
N/A | N/A | N/A | N/A | |||||
Mobile Solution with DS 500, Oil Check 500, PC 400, FA 510 |
N/A
Item # - 0554 8040 Description - CS Basic - data evaluation in graphic and table form - readout of the measured data via USB or Ethernet. License for 2 working places Item # - 0699 0080 Description - Residual oil measurement: Oil Check 500 - residual oil measurement of the vaporous oil content from 0,001…5 mg/m³, 43.5 .... 130.5 psi. High-precision PID-Sensor, innovative “Forced Pressure Variation“ measuring method, with integrated display, with 4...20 mA analog output and digital Modbus RTU interface, incl. calibration certificate Item # - 0554 6017 Description - Mobile transport trolley including roles (outer dimensions: 26.77 x 41.73 x 16.14 inch) (W x H x D) with firmly mounted components of Oil Check 400, PC 400, FA 510 Item # - Z699 0078 Description - Options:Integrated heating element for the stationary Oil Check 500. Keeps the gas temperature constantly above 68 F. Recommended for installations where the room temperature may fall below 68 F. Item # - Z699 7774 Description - Mobile sampling system consisting of 6.56 ft PTFE hose, quick coupling (oil- and grease-free) Item # - 0553 0104 Description - Connection cable for probes, 16 ft with open ends Item # - 0699 0040 Description - PC 400 particle counter up to 0.1 ?m for compressed air and gases, incl. pressure reducer/ sampling hose, calibration certificate, Modbus-RTU interface Item # - 0553 0104 Description - Connection cable for probes, 16 ft with open ends Item # - 0699 0510 Description - FA 510 Dew point sensor, -112 ... +68 Ftd Item # - 0699 3390 Description - Standard measuring chamber Item # - 0553 0104 Description - Connection cable for VA/FA series, 16 ft with open ends |
N/A | N/A | N/A | N/A | |||||
Portable Solution | N/A |
N/A
Item # - Z699 0174 Description - Portable sampling system consisting of 6.56 ft PTFE hose, quick coupling (oil- and grease-free) Item # - 0500 5012 Description - DS 500 mobile - intelligent chart recorder with 4 sensor inputs Item # - 0554 8040 Description - CS Basic - data evaluation in graphic and table form - readout of the measured data via USB or Ethernet. License for 2 working places |
N/A | N/A | N/A | |||||
Features |
N/A
|
N/A
|
N/A | N/A | N/A | |||||
Additional Information |
N/A
Measure compressed air quality according to ISO 8573 Residual Oil - Particles - Residual Moisture Residual oil content measurement - Oil Check 500 For permanent and highly precise measurement of the vaporous oil content from 0.001 mg/m³ to 5 mg/m³. Due to the low detection limit of 0.001 mg/ m³, the compressed air quality class 1 (ISO 8573) can be monitored. Particle counter PC 400 The highly precise, optical particle counter PC 400 measures particles from a size of 0.1 ?m and is therefore suitable for monitoring the compressed air quality class 1 (ISO 8573). Moisture - dew point sensor FA 510 FA 510 measures the pressure dew point down to -112 Ftd. Also in this case the continuous measurement takes care that alert is triggered immediately if the compressed air dryer breaks down. DS 500 - the intelligent chart recorder of the next generation The centerpiece of compressed air quality measurement is the chart recorder DS 500. It measures and documents the measured data of the sensors for residual oil content, particles and moisture. The measured values are indicated on a 7" color screen. The curve progressions from the beginning of the measurement can be viewed by an easy slide of the finger. The integrated data logger stores the measured values safely and reliably. The threshold value can be freely entered for each measured parameter. 4 alarm relays are available for automatic alarm in case of threshold value exceedance. Optionally DS 500 can be upgraded with up to 12 sensor inputs. For connection to a PLC DS 500 has an Ethernet interface as well as a RS 485 interface. The communication is done via the Modbus protocol. |
N/A
Oil Check 500 portable- Residual oil measurement of the vaporous oil content from 0.001...5 mg/m³, 43.5 ... 130.5 psi. High-precision PID sensor, innovative “Forced Pressure Variation“ measuring method, with integrated display, with 4...20 mA analog output and digital Modbus RTU interface, incl. calibration certificate, in a robust flight case. Connection cable ODU/ODU 16 ft Measure compressed air quality according to ISO 8573 Residual Oil - Particles - Residual Moisture Residual oil content measurement - Oil Check 500 For permanent and highly precise measurement of the vaporous oil content from 0.001 mg/m³ to 5 mg/m³. Due to the low detection limit of 0.001 mg/ m³, the compressed air quality class 1 (ISO 8573) can be monitored. Particle counter PC 400 The highly precise, optical particle counter PC 400 measures particles from a size of 0.1 ?m and is therefore suitable for monitoring the compressed air quality class 1 (ISO 8573). Moisture - dew point sensor FA 510 FA 510 measures the pressure dew point down to -112 Ftd. Also in this case the continuous measurement takes care that alert is triggered immediately if the compressed air dryer breaks down. DS 500 - the intelligent chart recorder of the next generation The centerpiece of compressed air quality measurement is the chart recorder DS 500. It measures and documents the measured data of the sensors for residual oil content, particles and moisture. The measured values are indicated on a 7" color screen. The curve progressions from the beginning of the measurement can be viewed by an easy slide of the finger. The integrated data logger stores the measured values safely and reliably. The threshold value can be freely entered for each measured parameter. 4 alarm relays are available for automatic alarm in case of threshold value exceedance. Optionally DS 500 can be upgraded with up to 12 sensor inputs. For connection to a PLC DS 500 has an Ethernet interface as well as a RS 485 interface. The communication is done via the Modbus protocol. |
N/A | N/A | N/A | |||||
|