Water Inlet & Outlet National Pipe Thread (NPT) |
N/A 1/2 in |
Thread Type |
N/A National Pipe Thread (NPT) |
Cooling Capacity |
N/A 6824 Btu/hr0.6 ton |
Total Installed Power |
N/A 1.3 kW |
Water Pump Power |
N/A 0.5 hp |
Tank Capacity |
N/A 6 gal |
Dimension A |
N/A 29 in |
Dimension B |
N/A 22 in |
Dimension C |
N/A 35 in |
Refrigerant Type |
N/A R410A |
Minimum Inlet Water Temperature |
N/A 32 ºF |
Maximum Inlet Water Temperature |
N/A 86 ºF |
Minimum Outlet Water Temperature |
N/A 32 ºF |
Maximum Outlet Water Temperature |
N/A 68 ºF |
Minimum Ambient Temperature |
N/A 23 ºF |
Maximum Ambient Temperature |
N/A 108 ºF |
Shipping Weight |
N/A 187 Pound |
Power Supply Voltage |
N/A 230 V |
Power Supply Phase |
N/A 1 |
Power Supply Frequency |
N/A 60 Hz |
N/A
Leading edge technology and hundreds of years of experience…nano-purification solutions, your world-class manufacturer of state-of-the-art compressed air and gas solutions and process cooling equipment to industry. |
Design |
N/A Our experienced team of design engineers are always looking for new and unique technologies and products to bring you the highest level of performance and lowest overall operating cost. |
Research and Development |
N/A Our R&D team endeavors to provide solutions that go beyond developing an existing product. They are continually researching new technologies which can provide unique advantages over competitive offerings. |
Manufacture |
N/A The reliable and energy saving nano C1 industrial process chillers are manufactured in a state of the art facility to the highest standards of build quality to ensure reliability and high levels of performance. |
Optimum Energy Efficiency |
N/A lower electricity consumption compared to other machines on the market |
Quality Components |
N/A CAREL microprocessor, Copeland Scroll™ compressors |
Easy to Install |
N/A adapts to any installation constraints, both inside and outside |
Space Saving Design |
N/A Fully packaged into a simple compact design, NCS will fit into the smallest spaces |
Easy Start-up |
N/A Fully integrated packaged solution with expansion tank and bypass |
Total Accessibility |
N/A All panels can be removed to facilitate maintenance |
Environmentally Friendly |
N/A closed water circuit, cycling chiller using environmentally friendly refrigerant boasts lowest electricity consumption on the market |
Manufacturing Quality |
N/A Meeting strict ISO 9001 certified specifications |
Air-cooled Condenser |
N/A Fitted with axial cooling fan with balanced aluminum blades and an air-cooled condenser in copper pipes and aluminum vanes. Reduces noise levels and improves ventilation air flow |
CAREL Microprocessor |
N/A The CAREL digital microprocessor continuously indicates water outlet temperature, operating instructions and various adjustable parameters and alarms |
NO FROST Evaporator |
N/A Patented tube in flexible shell heat exchanger is integral to the buffer vessel and protects against damage which can occur with improper setup or maintenance (1 external shell, 2 buffer tank, 3 flexible shell, 4 gas distributor, 5 feeding circuits, 6 ret |
Ventilation Grill |
N/A Includes a standard cleanable mesh panel filter to protect condenser |
Robust Construction |
N/A Aluminum sections and panels in plastic coated galvanized steel all mounted on an epoxy coated steel structural base (aluminum or stainless steel panels available as option) |
Energy Efficient & Reliable Compressor |
N/A C1 features Copeland Scroll™ compressors as standard on models NCS 0015 to 1504 US. Scrolls minimize power consumption, noise, vibration and moving parts while maximizing reliability and resistance to liquid refrigerant returns |
Closed Circuit Installation (Standard) |
N/A Expansion tanks are required for all closed circuit installations. When multiple chillers are installed in parallel, the expansion tanks must be automatic. |
Open Circuit Installation (Optional) |
N/A Expansion tanks are not required for open circuit installations. Open circuits also typically use an external pump so, the internal pump may not be required. |
Standard Features |
N/A
|
More Capabilities |
N/A
|
Optional Features |
N/A
|
Note for Inlet Water Temperature |
N/A Assumes 45 ºF cooling water supply, 55 ºF cooling water return and 95 ºF ambient temperature. For all other conditions refer to the correction factors. |
Note for Outlet Water Temperature |
N/A Assumes 45 ºF cooling water supply, 55 ºF cooling water return and 95 ºF ambient temperature. For all other conditions refer to the correction factors. |
Note for Ambient Temperature |
N/A Assumes 45 ºF cooling water supply, 55 ºF cooling water return and 95 ºF ambient temperature. For all other conditions refer to the correction factors. |
Note for Power Supply |
N/A All models are 60 Hz. Protection class IP55 standard except for NCS 0002 - 0006 US IP44 standard. |
Note for Cooling Capacity |
N/A Assumes 45 ºF cooling water supply, 55 ºF cooling water return and 95 ºF ambient temperature. For all other conditions refer to the correction factors. |
Note for Total Installed Power |
N/A Total nominal absorbed power by (all) compressor(s) at rated inlet conditions using 230/1/60 or 460/3/60 power supply as applicable. |
Note for Evaporator Correction Factor |
N/A Assumes no change to condenser inlet water temperature. |
Note for Condenser Correction Factor |
N/A Assumes no change to evaporator outlet water temperature. |
Note for Correction Factors |
N/A To be used as a guide only. All applications should be confirmed by nano. |
Note |
N/A Additional specifications available, consult factory |
Correction Factor at 30 Degree Fahrenheit (ºF) Water Outlet Temperature |
N/A 0.68 |
Correction Factor at 35 Degree Fahrenheit (ºF) Water Outlet Temperature |
N/A 0.79 |
Correction Factor at 40 Degree Fahrenheit (ºF) Water Outlet Temperature |
N/A 0.91 |
Correction Factor at 45 Degree Fahrenheit (ºF) Water Outlet Temperature |
N/A 1 |
Correction Factor at 50 Degree Fahrenheit (ºF) Water Outlet Temperature |
N/A 1.10 |
Correction Factor at 55 Degree Fahrenheit (ºF) Water Outlet Temperature |
N/A 1.19 |
Correction Factor at 60+ Degree Fahrenheit (ºF) Water Outlet Temperature |
N/A 1.27 |
Correction Factor at 75 Degree Fahrenheit (ºF) Ambient Temperature |
N/A 1.18 |
Correction Factor at 80 Degree Fahrenheit (ºF) Ambient Temperature |
N/A 1.14 |
Correction Factor at 85 Degree Fahrenheit (ºF) Ambient Temperature |
N/A 1.11 |
Correction Factor at 90 Degree Fahrenheit (ºF) Ambient Temperature |
N/A 1.04 |
Correction Factor at 95 Degree Fahrenheit (ºF) Ambient Temperature |
N/A 1 |
Correction Factor at 100 Degree Fahrenheit (ºF) Ambient Temperature |
N/A 0.96 |
Correction Factor at 7 Degree Fahrenheit (ºF) Evaporator ΔT |
N/A 0.993 |
Correction Factor at 105 Degree Fahrenheit (ºF) Ambient Temperature |
N/A 0.92 |
Correction Factor at 9 Degree Fahrenheit (ºF) Evaporator ΔT |
N/A 1 |
Correction Factor at 10 Degree Fahrenheit (ºF) Evaporator ΔT |
N/A 1.003 |
Correction Factor at 12 Degree Fahrenheit (ºF) Evaporator ΔT |
N/A 1.009 |
Correction Factor at 14 Degree Fahrenheit (ºF) Evaporator ΔT |
N/A 1.015 |
Correction Factor at 16 Degree Fahrenheit (ºF) Evaporator ΔT |
N/A 1.021 |
Correction Factor at 18 Degree Fahrenheit (ºF) Evaporator ΔT |
N/A 1.025 |
Correction Factor at 10 Degree Fahrenheit (ºF) Condenser ΔT |
N/A 1 |
Correction Factor at 12.5 Degree Fahrenheit (ºF) Condenser ΔT |
N/A 0.99 |
Correction Factor at 15 Degree Fahrenheit (ºF) Condenser ΔT |
N/A 0.98 |
Correction Factor at 17.5 Degree Fahrenheit (ºF) Condenser ΔT |
N/A 0.97 |
Correction Factor at 20 Degree Fahrenheit (ºF) Condenser ΔT |
N/A 0.96 |
Correction Factor at 22.5 Degree Fahrenheit (ºF) Condenser ΔT |
N/A 0.95 |
Correction Factor at 25 Degree Fahrenheit (ºF) Condenser ΔT |
N/A 0.93 |
Correction Factor at 0 Percent (%) Propylene Glycol |
N/A 1 |
Correction Factor at 10 Percent (%) Propylene Glycol |
N/A 0.99 |
Correction Factor at 20 Percent (%) Propylene Glycol |
N/A 0.98 |
Correction Factor at 30 Percent (%) Propylene Glycol |
N/A 0.97 |
Correction Factor at 40 Percent (%) Propylene Glycol |
N/A 0.96 |
Correction Factor at 45 Percent (%) Propylene Glycol |
N/A 0.95 |
Correction Factor at 50 Percent (%) Propylene Glycol |
N/A 0.93 |