Correction Factor at 30 Degree Fahrenheit (ºF) Water Outlet Temperature
|
|
0.68
|
|
Correction Factor at 35 Degree Fahrenheit (ºF) Water Outlet Temperature
|
|
0.79
|
|
Correction Factor at 40 Degree Fahrenheit (ºF) Water Outlet Temperature
|
|
0.91
|
|
Correction Factor at 45 Degree Fahrenheit (ºF) Water Outlet Temperature
|
|
1
|
|
Correction Factor at 50 Degree Fahrenheit (ºF) Water Outlet Temperature
|
|
1.09
|
|
Correction Factor at 55 Degree Fahrenheit (ºF) Water Outlet Temperature
|
|
1.19
|
|
Correction Factor at 60 Degree Fahrenheit (ºF) Water Outlet Temperature
|
|
1.27
|
|
Correction Factor at 80 Degree Fahrenheit (ºF) Ambient Temperature
|
|
1.11
|
|
Correction Factor at 85 Degree Fahrenheit (ºF) Ambient Temperature
|
|
1.08
|
|
Correction Factor at 90 Degree Fahrenheit (ºF) Ambient Temperature
|
|
1.04
|
|
Correction Factor at 95 Degree Fahrenheit (ºF) Ambient Temperature
|
|
1
|
|
Correction Factor at 100 Degree Fahrenheit (ºF) Ambient Temperature
|
|
0.93
|
|
Correction Factor at 105 Degree Fahrenheit (ºF) Ambient Temperature
|
|
0.91
|
|
Correction Factor at 113 Degree Fahrenheit (ºF) Ambient Temperature
|
|
0.83
|
|
Correction Factor at 0 Percent (%) Ethylene Glycol
|
|
1
|
|
Correction Factor at 10 Percent (%) Ethylene Glycol
|
|
0.99
|
|
Correction Factor at 20 Percent (%) Ethylene Glycol
|
|
0.98
|
|
Correction Factor at 30 Percent (%) Ethylene Glycol
|
|
0.97
|
|
Correction Factor at 40 Percent (%) Ethylene Glycol
|
|
0.96
|
|
Correction Factor at 45 Percent (%) Ethylene Glycol
|
|
0.95
|
|
Correction Factor at 50 Percent (%) Ethylene Glycol
|
|
0.94
|
|