VA 570 is supplied with an integrated measuring section. The measuring sections are available in flanged version or with R resp. NPT thread.

A special feature is the removable measuring head. So the measuring unit can be removed easily and quickly for calibration or cleaning purposes without having to dismount the measuring section intricately. During this period the measuring section is sealed by a closing cap (accessory).
Unit of Measure

Financing

Approve Payments

N/A Finance with Approve Payments

Specifications

Measuring Range

N/A Up to 164 ft/s, Low-Speed Version Up to 304 ft/s, Standard Version Up to 607 ft/s, Maximum Version Up to 735 ft/s, High-Speed Version

Note for Measuring Range

N/A All measured values related to DIN 1343 standard conditions 32 ºF and 14.7 psi ex works.

Accuracy

N/A ± 0.3% of Full Scale (F.S.) ± 1.5% of Measured Value (M.V.)

Accuracy on Request

N/A ± 1.0% of Measured Value (M.V.) ± 0.3% of Full Scale (F.S.)

Accuracy Indications

N/A Relative to Ambient Temperature 71.6 ºF +2 ºF, System Pressure 6 bar

Repeatability

N/A 0.25% of Measured Value (M.V.) in Case of Correct Mounting (Mounting Aid, Position, Inlet Section)

Measuring Principle

N/A Thermal Mass Flow Sensor

Response Time

N/A t 90 <3 sec

Operating/Ambient Temperature Range

N/A -4 to 158 ºF

Media Temperature Range

N/A -4 to 356 ºF

Media Temperature Range (ATEX Version)

N/A -4 to 248 ºF

Adjustment Possibilities via Display, External Hand- Held Device PI 500, PC Service Software, Remote Diagnosis

N/A Nm³/h, Nm³/min, Nl/min, l/s, ft/min, cfm, kg/h, kg/min, inner diameter, reference conditions ºC/ºF, mbar/hPa, zero point correction, leak flow volume suppression, scaling analog output 4...20 mA, pulse/alarm, error codes etc.

Standard Outputs

N/A 1 x 4 to 20 mA Analog Output (Electrically Not Isolated) Pulse Output RS 485 (Modbus-RTU)

Optional Outputs

N/A 2 x 4 to 20 mA Active HART M-Bus Mod- bus TCP Profibus DP Profinet

Burden

N/A <500 Ω

Additional Average Value Calculation

N/A For all parameters freely adjustable from 1 minute up to 1 day, e. g. 1/2 hours average value, average day value

Protection Class

N/A Ingress Protection (IP 64) for ATEX II 2D Ex tb IIIC T90°C Db Ingress Protection (IP 67)

Housing Material

N/A Die-Cast Aluminum

Sensor Tube Material

N/A Stainless Steel 1.4404

Operating Pressure

N/A 232 psi

Special Version Operating Pressure

N/A 580 psi

Direct Current (DC) Supply Voltage

N/A 18 to 36 V

Power Supply

N/A 5 W

Approval

N/A ATEX II 2G Ex db IIC T4 Gb ATEX II 2D Ex tb IIIC T90 ºC Db DVGW

Measuring Range

Low-Speed Air Flow (164 Feet Per Seconds (ft/s))

N/A 765 L/min450 ft³/min

Standard Air Flow (304 Feet Per Seconds (ft/s))

N/A 1420 m³/h835 ft³/min

Maximum Air Flow (607 Feet Per Seconds (ft/s))

N/A 2840 m³/h1670 ft³/min

High-Speed Air Flow (735 Feet Per Seconds (ft/s))

N/A 3440 m³/h2025 ft³/min

Note for Air Flow

N/A Reference conditions DIN 1945 / ISO 1217: 68 ºF, 14 psi

Low-Speed Argon (Ar) Flow (164 Feet Per Seconds (ft/s))

N/A 1200 L/min705 ft³/min

Standard Argon (Ar) Flow (304 Feet Per Seconds (ft/s))

N/A 2225 m³/h1310 ft³/min

Maximum Argon (Ar) Flow (607 Feet Per Seconds (ft/s))

N/A 4440 m³/h2615 ft³/min

High-Speed Argon (Ar) Flow (735 Feet Per Seconds (ft/s))

N/A 5380 m³/h3165 ft³/min

Note for Argon (Ar) Flow

N/A Setting to DIN 1343: 32 ºF, 14.7 psi

Low-Speed Carbon Dioxide (CO2) Flow (164 Feet Per Seconds (ft/s))

N/A 760 L/min445 ft³/min

Standard Carbon Dioxide (CO2) Flow (304 Feet Per Seconds (ft/s))

N/A 1405 m³/h825 ft³/min

Maximum Carbon Dioxide (CO2) Flow (607 Feet Per Seconds (ft/s))

N/A 2810 m³/h1655 ft³/min

High-Speed Carbon Dioxide (CO2) Flow (735 Feet Per Seconds (ft/s)

N/A 3405 m³/h2000 ft³/min

Note for Carbon Dioxide (CO2) Flow

N/A Setting to DIN 1343: 32 ºF, 14.7 psi

Low-Speed Nitrogen (N2) Flow (164 Feet Per Seconds (ft/s))

N/A 705 L/min415 ft³/min

Standard Nitrogen (N2) Flow (304 Feet Per Seconds (ft/s))

N/A 1305 m³/h770 ft³/min

Maximum Nitrogen (N2) Flow (607 Feet Per Seconds (ft/s))

N/A 2610 m³/h1535 ft³/min

High-Speed Nitrogen (N2) Flow (735 Feet Per Seconds (ft/s))

N/A 3165 m³/h1860 ft³/min

Note for Nitrogen (N2) Flow

N/A Setting to DIN 1343: 32 ºF, 14.7 psi

Low-Speed Oxygen (O2) Flow (164 Feet Per Seconds (ft/s))

N/A 730 L/min430 ft³/min

Standard Oxygen (O2) Flow (304 Feet Per Seconds (ft/s))

N/A 1355 m³/h795 ft³/min

Maximum Oxygen (O2) Flow (607 Feet Per Seconds (ft/s))

N/A 2710 m³/h1590 ft³/min

High-Speed Oxygen (O2) Flow (735 Feet Per Seconds (ft/s))

N/A 3280 m³/h1930 ft³/min

Note for Oxygen (O2) Flow

N/A Setting to DIN 1343: 32 ºF, 14.7 psi

Low-Speed Nitrous Oxide (N2O) Flow (164 Feet Per Seconds (ft/s))

N/A 750 L/min440 ft³/min

Standard Nitrous Oxide (N2O) Flow (304 Feet Per Seconds (ft/s))

N/A 1395 m³/h820 ft³/min

Maximum Nitrous Oxide (N2O) Flow (607 Feet Per Seconds (ft/s))

N/A 2785 m³/h1640 ft³/min

High-Speed Nitrous Oxide (N2O) Flow (735 Feet Per Seconds (ft/s))

N/A 3375 m³/h1985 ft³/min

Note for Nitrous Oxide (N2O) Flow

N/A Setting to DIN 1343: 32 ºF, 14.7 psi

Low-Speed Natural Gas (NG) Flow (164 Feet Per Seconds (ft/s))

N/A 450 L/min265 ft³/min

Standard Natural Gas (NG) Flow (304 Feet Per Seconds (ft/s))

N/A 840 m³/h495 ft³/min

Maximum Natural Gas (NG) Flow (607 Feet Per Seconds (ft/s))

N/A 1680 m³/h985 ft³/min

High-Speed Natural Gas (NG) Flow (735 Feet Per Seconds (ft/s))

N/A 2035 m³/h1195 ft³/min

Note for Natural Gas (NG) Flow

N/A Setting to DIN 1343: 32 ºF, 14.7 psi

Flange

Flange Pipe Size

N/A 3 in

Flange Outer Pipe Diameter

N/A 88.9 mm

Flange Inner Pipe Diameter

N/A 80.9 mm

Dimension L (Flange)

N/A 18.7 in

Note for Dimension L (Flange)

N/A Attention: Shortened inlet section. Please observe the recommended minimum inlet section (length = 15 x inner diameter) on site.

Dimension L1 (Flange)

N/A 10.83 in

Dimension H (Flange)

N/A 12.91 in

Dimension H1 (Flange)

N/A 8.98 in

Diameter D (Flange)

N/A 200 mm

Diameter K (Flange)

N/A 160 mm

Number of Diameter L (Flange)

N/A 8

Diameter L (Flange)

N/A 18 mm

Connection to Different Bus Systems Options

Connection to Different Bus Systems Options

N/A There are different options available for connection to modern Bus systems:
  • Ethernet interface (Modbus-TCP) / PoE
  • M-BUS
  • Modbus-RTU
  • Profibus DP interface (in process)
  • Profinet interface (in process)
  • HART (in process)

Special Measurement Technology Features

Special Measurement Technology Features

N/A
  • 4 values on the display: Flow, total consumption, velocity, temperature. Units freely adjustable
  • All measured values, settings such as gas type, inner diameter, serial number and so on can be accessed via Modbus-RTU
  • Comprehensive diagnostic functions readable on the display or remote access via Modbus such as calibration cycle, error codes, serial number
  • Notification in case of exceeding the calibration cycle
  • Standard version accuracy 1.5% of m.v. ± 0.3% of f.s.
  • Precision version accuracy 1.0% of m.v. ± 0.3% of f.s
  • Measuring span of 1 : 1000 (0.33 ft/s up to 735 ft/s)
  • Configuration and diagnosis via display, hand-held device PI 500, PC service software on-site
  • Gas type (air, nitrogen, oxygen, argon and so on) freely adjustable via PC service software or external device DS 400, DS 500, PI 500
  • Reference conditions ºC and PST / hPA freely adjustable
  • In-Situ adjustment, leak flow volume suppression
  • Pressure loss negligible

Special Mechanical Features

Special Mechanical Features

N/A
  • Robust impact-proof aluminum die cast housing for the outdoor area IP 67
  • All wetted parts made from stainless steel 1.4404
  • On request with DVGW approval for natural gas (up to 232 psi)
  • Pressure range up to 232 psi, special version up to 580 psi
  • Media temperature range up to 356 ºF (ATEX version up to 248 ºF)
  • No moveable parts, no wear
  • Sensor tip very robust, easy to clean
  • Housing rotatable, display rotatable by -356 ºF

Additional Information

N/A The screwing with a centring device is designed such that the sensor is positioned accurately in the center when screwing it into the measuring section; furthermore, it enables an exact positioning in the flow direction. This eliminates unnecessary measuring faults.