VA 570 is supplied with an integrated measuring section. The measuring sections are available in flanged version or with R resp. NPT thread.

A special feature is the removable measuring head. So the measuring unit can be removed easily and quickly for calibration or cleaning purposes without having to dismount the measuring section intricately. During this period the measuring section is sealed by a closing cap (accessory).
Unit of Measure

Financing

Approve Payments

N/A Finance with Approve Payments

Specifications

Measuring Range

N/A Up to 164 ft/s, Low-Speed Version Up to 304 ft/s, Standard Version Up to 607 ft/s, Maximum Version Up to 735 ft/s, High-Speed Version

Note for Measuring Range

N/A All measured values related to DIN 1343 standard conditions 32 ºF and 14.7 psi ex works.

Accuracy

N/A ± 0.3% of Full Scale (F.S.) ± 1.5% of Measured Value (M.V.)

Accuracy on Request

N/A ± 1.0% of Measured Value (M.V.) ± 0.3% of Full Scale (F.S.)

Accuracy Indications

N/A Relative to Ambient Temperature 71.6 ºF +2 ºF, System Pressure 6 bar

Repeatability

N/A 0.25% of Measured Value (M.V.) in Case of Correct Mounting (Mounting Aid, Position, Inlet Section)

Measuring Principle

N/A Thermal Mass Flow Sensor

Response Time

N/A t 90 <3 sec

Operating/Ambient Temperature Range

N/A -4 to 158 ºF

Media Temperature Range

N/A -4 to 356 ºF

Media Temperature Range (ATEX Version)

N/A -4 to 248 ºF

Adjustment Possibilities via Display, External Hand- Held Device PI 500, PC Service Software, Remote Diagnosis

N/A Nm³/h, Nm³/min, Nl/min, l/s, ft/min, cfm, kg/h, kg/min, inner diameter, reference conditions ºC/ºF, mbar/hPa, zero point correction, leak flow volume suppression, scaling analog output 4...20 mA, pulse/alarm, error codes etc.

Standard Outputs

N/A 1 x 4 to 20 mA Analog Output (Electrically Not Isolated) Pulse Output RS 485 (Modbus-RTU)

Optional Outputs

N/A 2 x 4 to 20 mA Active HART M-Bus Mod- bus TCP Profibus DP Profinet

Burden

N/A <500 Ω

Additional Average Value Calculation

N/A For all parameters freely adjustable from 1 minute up to 1 day, e. g. 1/2 hours average value, average day value

Protection Class

N/A Ingress Protection (IP 64) for ATEX II 2D Ex tb IIIC T90°C Db Ingress Protection (IP 67)

Housing Material

N/A Die-Cast Aluminum

Sensor Tube Material

N/A Stainless Steel 1.4404

Operating Pressure

N/A 232 psi

Special Version Operating Pressure

N/A 580 psi

Direct Current (DC) Supply Voltage

N/A 18 to 36 V

Power Supply

N/A 5 W

Approval

N/A ATEX II 2G Ex db IIC T4 Gb ATEX II 2D Ex tb IIIC T90 ºC Db DVGW

Measuring Range

Low-Speed Air Flow (164 Feet Per Seconds (ft/s))

N/A 320 L/min190 ft³/min

Standard Air Flow (304 Feet Per Seconds (ft/s))

N/A 600 m³/h350 ft³/min

Maximum Air Flow (607 Feet Per Seconds (ft/s))

N/A 1195 m³/h700 ft³/min

High-Speed Air Flow (735 Feet Per Seconds (ft/s))

N/A 1450 m³/h850 ft³/min

Note for Air Flow

N/A Reference conditions DIN 1945 / ISO 1217: 68 ºF, 14 psi

Low-Speed Argon (Ar) Flow (164 Feet Per Seconds (ft/s))

N/A 505 L/min295 ft³/min

Standard Argon (Ar) Flow (304 Feet Per Seconds (ft/s))

N/A 935 m³/h550 ft³/min

Maximum Argon (Ar) Flow (607 Feet Per Seconds (ft/s))

N/A 1870 m³/h1100 ft³/min

High-Speed Argon (Ar) Flow (735 Feet Per Seconds (ft/s))

N/A 2265 m³/h1330 ft³/min

Note for Argon (Ar) Flow

N/A Setting to DIN 1343: 32 ºF, 14.7 psi

Low-Speed Carbon Dioxide (CO2) Flow (164 Feet Per Seconds (ft/s))

N/A 320 L/min185 ft³/min

Standard Carbon Dioxide (CO2) Flow (304 Feet Per Seconds (ft/s))

N/A 590 m³/h345 ft³/min

Maximum Carbon Dioxide (CO2) Flow (607 Feet Per Seconds (ft/s))

N/A 1185 m³/h695 ft³/min

High-Speed Carbon Dioxide (CO2) Flow (735 Feet Per Seconds (ft/s)

N/A 1430 m³/h840 ft³/min

Note for Carbon Dioxide (CO2) Flow

N/A Setting to DIN 1343: 32 ºF, 14.7 psi

Low-Speed Nitrogen (N2) Flow (164 Feet Per Seconds (ft/s))

N/A 295 L/min175 ft³/min

Standard Nitrogen (N2) Flow (304 Feet Per Seconds (ft/s))

N/A 550 m³/h320 ft³/min

Maximum Nitrogen (N2) Flow (607 Feet Per Seconds (ft/s))

N/A 1100 m³/h645 ft³/min

High-Speed Nitrogen (N2) Flow (735 Feet Per Seconds (ft/s))

N/A 1330 m³/h780 ft³/min

Note for Nitrogen (N2) Flow

N/A Setting to DIN 1343: 32 ºF, 14.7 psi

Low-Speed Oxygen (O2) Flow (164 Feet Per Seconds (ft/s))

N/A 305 L/min180 ft³/min

Standard Oxygen (O2) Flow (304 Feet Per Seconds (ft/s))

N/A 570 m³/h335 ft³/min

Maximum Oxygen (O2) Flow (607 Feet Per Seconds (ft/s))

N/A 1140 m³/h670 ft³/min

High-Speed Oxygen (O2) Flow (735 Feet Per Seconds (ft/s))

N/A 1380 m³/h810 ft³/min

Note for Oxygen (O2) Flow

N/A Setting to DIN 1343: 32 ºF, 14.7 psi

Low-Speed Nitrous Oxide (N2O) Flow (164 Feet Per Seconds (ft/s))

N/A 315 L/min185 ft³/min

Standard Nitrous Oxide (N2O) Flow (304 Feet Per Seconds (ft/s))

N/A 585 m³/h345 ft³/min

Maximum Nitrous Oxide (N2O) Flow (607 Feet Per Seconds (ft/s))

N/A 1170 m³/h690 ft³/min

High-Speed Nitrous Oxide (N2O) Flow (735 Feet Per Seconds (ft/s))

N/A 1420 m³/h835 ft³/min

Note for Nitrous Oxide (N2O) Flow

N/A Setting to DIN 1343: 32 ºF, 14.7 psi

Low-Speed Natural Gas (NG) Flow (164 Feet Per Seconds (ft/s))

N/A 190 L/min110 ft³/min

Standard Natural Gas (NG) Flow (304 Feet Per Seconds (ft/s))

N/A 355 m³/h205 ft³/min

Maximum Natural Gas (NG) Flow (607 Feet Per Seconds (ft/s))

N/A 705 m³/h415 ft³/min

High-Speed Natural Gas (NG) Flow (735 Feet Per Seconds (ft/s))

N/A 855 m³/h500 ft³/min

Note for Natural Gas (NG) Flow

N/A Setting to DIN 1343: 32 ºF, 14.7 psi

Thread

Connection Thread

N/A R 2 in.

Thread Outer Pipe Diameter

N/A 60.3 mm

Thread Inner Pipe Diameter

N/A 53.1 mm

Dimension L (Thread)

N/A 18.70 Inch

Note for Dimension L (Thread)

N/A Attention: Shortened inlet section. Please observe the recommended minimum inlet section (length = 15 x inner diameter) on site!

Dimension L1 (Thread)

N/A 10.83 in

Dimension H (Thread)

N/A 9.76 in

Dimension H1 (Thread)

N/A 8.58 in

Dimension A (Thread)

N/A 1.18 in

Connection to Different Bus Systems Options

Connection to Different Bus Systems Options

N/A There are different options available for connection to modern Bus systems:
  • Ethernet interface (Modbus-TCP) / PoE
  • M-BUS
  • Modbus-RTU
  • Profibus DP interface (in process)
  • Profinet interface (in process)
  • HART (in process)

Special Measurement Technology Features

Special Measurement Technology Features

N/A
  • 4 values on the display: Flow, total consumption, velocity, temperature. Units freely adjustable
  • All measured values, settings such as gas type, inner diameter, serial number and so on can be accessed via Modbus-RTU
  • Comprehensive diagnostic functions readable on the display or remote access via Modbus such as calibration cycle, error codes, serial number
  • Notification in case of exceeding the calibration cycle
  • Standard version accuracy 1.5% of m.v. ± 0.3% of f.s.
  • Precision version accuracy 1.0% of m.v. ± 0.3% of f.s
  • Measuring span of 1 : 1000 (0.33 ft/s up to 735 ft/s)
  • Configuration and diagnosis via display, hand-held device PI 500, PC service software on-site
  • Gas type (air, nitrogen, oxygen, argon and so on) freely adjustable via PC service software or external device DS 400, DS 500, PI 500
  • Reference conditions ºC and PST / hPA freely adjustable
  • In-Situ adjustment, leak flow volume suppression
  • Pressure loss negligible

Special Mechanical Features

Special Mechanical Features

N/A
  • Robust impact-proof aluminum die cast housing for the outdoor area IP 67
  • All wetted parts made from stainless steel 1.4404
  • On request with DVGW approval for natural gas (up to 232 psi)
  • Pressure range up to 232 psi, special version up to 580 psi
  • Media temperature range up to 356 ºF (ATEX version up to 248 ºF)
  • No moveable parts, no wear
  • Sensor tip very robust, easy to clean
  • Housing rotatable, display rotatable by -356 ºF

Additional Information

N/A The screwing with a centring device is designed such that the sensor is positioned accurately in the center when screwing it into the measuring section; furthermore, it enables an exact positioning in the flow direction. This eliminates unnecessary measuring faults.