Parameters |
N/A m³/h, CFM (1000 mbar, 20 ºC) in case of compressed air or Nm³/h, Nl/min (1013 mbar, 0 ºC) in case of gases |
Units Adjustable Via Keys at Display |
N/A CFM ft/min g/s kg/h kg/min l/s lb/h lb/min m/s m³/h m³/min |
Sensor |
N/A Thermal Mass Flow Sensor |
Measured Medium |
N/A Air Gases |
Gas Types are Adjustable Over CS Service Software or CS Data Logger |
N/A Air Argon CO2 Nitrogen Oxygen |
Accuracy |
N/A ± 0.3% of Full Scale (F.S.) ± 1.5% of Measured Value (M.V.) |
Accuracy on Request |
N/A ± 1.0% of Measured Value (M.V.) ± 0.3% of Full Scale (F.S.) |
Operating Temperature |
N/A -22 to 176 ºF |
Operating Temperature with Pressure Sensor |
N/A -25 to 349 ºF |
Operating Pressure |
N/A -1 to 232 psi |
Optional Pressure |
N/A Up to Nominal Pressure (PN) 40 |
Digital Output |
N/A M-Bus Modbus-Remote Terminal Unit (RTU) Optional: Ethernet Interface (PoE) RS 485 Interface |
Analog Output for Cubic Feet Per Minute (CFM) |
N/A 4 to 20 mA |
Pulse Output |
N/A 1 pulse per CF or per liter electrically isolated. Pulse weight can be set on the display. Alternatively, the pulse output can be used as an alarm relay. |
Direct Current (DC) Supply Voltage |
N/A 18 to 36 V |
Power Supply |
N/A 5 W |
Burden |
N/A <500 Ω |
Housing Material |
N/A Polycarbonate |
Protection Rating |
N/A Ingress Protection (IP 65) |
Material |
N/A Stainless Steel 1.4301 |
Mounting Position |
N/A Any |
Dimension L (Thread) |
N/A 475 mm18.7 in |
Low-Speed Air Flow (164 Feet Per Seconds (ft/s)) |
N/A 320 L/min190 ft³/min |
Standard Air Flow (304 Feet Per Seconds (ft/s)) |
N/A 600 m³/h350 ft³/min |
Maximum Air Flow (607 Feet Per Seconds (ft/s)) |
N/A 1195 m³/h700 ft³/min |
High-Speed Air Flow (735 Feet Per Seconds (ft/s)) |
N/A 1450 m³/h850 ft³/min |
Note for Air Flow |
N/A Reference conditions DIN 1945 / ISO 1217: 68 ºF, 14 psi |
Low-Speed Argon (Ar) Flow (164 Feet Per Seconds (ft/s)) |
N/A 505 L/min295 ft³/min |
Standard Argon (Ar) Flow (304 Feet Per Seconds (ft/s)) |
N/A 935 m³/h550 ft³/min |
Maximum Argon (Ar) Flow (607 Feet Per Seconds (ft/s)) |
N/A 1870 m³/h1100 ft³/min |
High-Speed Argon (Ar) Flow (735 Feet Per Seconds (ft/s)) |
N/A 2265 m³/h1330 ft³/min |
Note for Argon (Ar) Flow |
N/A Setting to DIN 1343: 32 ºF, 14.7 psi |
Low-Speed Carbon Dioxide (CO2) Flow (164 Feet Per Seconds (ft/s)) |
N/A 320 L/min185 ft³/min |
Standard Carbon Dioxide (CO2) Flow (304 Feet Per Seconds (ft/s)) |
N/A 590 m³/h345 ft³/min |
Maximum Carbon Dioxide (CO2) Flow (607 Feet Per Seconds (ft/s)) |
N/A 1185 m³/h695 ft³/min |
High-Speed Carbon Dioxide (CO2) Flow (735 Feet Per Seconds (ft/s) |
N/A 1430 m³/h840 ft³/min |
Note for Carbon Dioxide (CO2) Flow |
N/A Setting to DIN 1343: 32 ºF, 14.7 psi |
Low-Speed Nitrogen (N2) Flow (164 Feet Per Seconds (ft/s)) |
N/A 505 L/min300 ft³/min |
Standard Nitrogen (N2) Flow (304 Feet Per Seconds (ft/s)) |
N/A 550 m³/h320 ft³/min |
Maximum Nitrogen (N2) Flow (607 Feet Per Seconds (ft/s)) |
N/A 1100 m³/h645 ft³/min |
High-Speed Nitrogen (N2) Flow (735 Feet Per Seconds (ft/s)) |
N/A 1330 m³/h780 ft³/min |
Note for Nitrogen (N2) Flow |
N/A Setting to DIN 1343: 32 ºF, 14.7 psi |
Low-Speed Oxygen (O2) Flow (164 Feet Per Seconds (ft/s)) |
N/A 305 L/min180 ft³/min |
Standard Oxygen (O2) Flow (304 Feet Per Seconds (ft/s)) |
N/A 570 m³/h335 ft³/min |
Maximum Oxygen (O2) Flow (607 Feet Per Seconds (ft/s)) |
N/A 1140 m³/h670 ft³/min |
High-Speed Oxygen (O2) Flow (735 Feet Per Seconds (ft/s)) |
N/A 1380 m³/h810 ft³/min |
Note for Oxygen (O2) Flow |
N/A Setting to DIN 1343: 32 ºF, 14.7 psi |
Low-Speed Nitrous Oxide (N2O) Flow (164 Feet Per Seconds (ft/s)) |
N/A 315 L/min185 ft³/min |
Standard Nitrous Oxide (N2O) Flow (304 Feet Per Seconds (ft/s)) |
N/A 585 m³/h345 ft³/min |
Maximum Nitrous Oxide (N2O) Flow (607 Feet Per Seconds (ft/s)) |
N/A 1170 m³/h690 ft³/min |
High-Speed Nitrous Oxide (N2O) Flow (735 Feet Per Seconds (ft/s)) |
N/A 1420 m³/h835 ft³/min |
Note for Nitrous Oxide (N2O) Flow |
N/A Setting to DIN 1343: 32 ºF, 14.7 psi |
Low-Speed Natural Gas (NG) Flow (164 Feet Per Seconds (ft/s)) |
N/A 190 L/min110 ft³/min |
Standard Natural Gas (NG) Flow (304 Feet Per Seconds (ft/s)) |
N/A 355 m³/h205 ft³/min |
Maximum Natural Gas (NG) Flow (607 Feet Per Seconds (ft/s)) |
N/A 705 m³/h415 ft³/min |
High-Speed Natural Gas (NG) Flow (735 Feet Per Seconds (ft/s)) |
N/A 855 m³/h500 ft³/min |
Note for Natural Gas (NG) Flow |
N/A Setting to DIN 1343: 32 ºF, 14.7 psi |
Measuring Section |
N/A 2 in |
Flange Outer Pipe Diameter |
N/A 60.3 mm2.37 in |
Flange Inner Pipe Diameter |
N/A 53.1 mm2.09 in |
Dimension L (Flange) |
N/A 18.7 in |
Note for Dimension L (Flange) |
N/A Attention: Shortened inlet section. Please observe the recommended minimum inlet section (length = 15 x inner diameter) on site. |
Dimension L1 (Flange) |
N/A 10.83 in |
Dimension H (Flange) |
N/A 9.7 in |
Dimension H1 (Flange) |
N/A 6.5 in |
Diameter D (Flange) |
N/A 165 mm |
Diameter K (Flange) |
N/A 125 mm |
Number of Diameter L (Flange) |
N/A 4 |
Diameter L (Flange) |
N/A 18 mm |
Connection Thread |
N/A R 2 in. |
Thread Outer Pipe Diameter |
N/A 60.3 mm2.37 in |
Thread Inner Pipe Diameter |
N/A 53.1 mm2.09 in |
Note for Dimension L (Thread) |
N/A Attention: Shortened inlet section. Please observe the recommended minimum inlet section (length = 15 x inner diameter) on site! |
Dimension L1 (Thread) |
N/A 10.8 in275 mm |
Dimension H (Thread) |
N/A 7.7 in195.9 mm |
Dimension H1 (Thread) |
N/A 6.5 in165.7 mm |
Dimension A (Thread) |
N/A 1.1 in30 mm |
Connection to Different Bus Systems Options |
N/A
There are different options available for connection to modern Bus systems:
|
With a Key Stroke |
N/A
|
Options |
N/A
Bi-directional measurement. Blue or green arrows in the display indicate the direction of flow. A meter reading is available for each flow direction. |
Application-Technological Features |
N/A
|
N/A
Modbus-RTU output |