Display: High-contrast, backlit
Alarms: Visual: LEDs Audible: Piezoelectric horn, 95 dB at 2 feet
Alarm Relays: 5 programmable gas relays plus fault. All relays are programmable latching or non-latching, dry SPDT, 10 amps (resistive load only) at 110 VAC.
Operating Power: 100 to 240 VAC and/or 12 VDC, 15 Watts
Sample Inlet Connection: Female quick release, supplied with male quick release for 1/4″ I.D. tubing. Tubing available from ENMET on request
Flow Rate: 1 Lpm (pump/internal sensors)
Enclosure: Thermoplastic box with clear, hinged front cover, designed for NEMA 12 and 4X
Dimensions: 9.3 W x 11.9 H x 7.8 D inches (21.3 W x 30.3 H x 15.4 D cm)
Weight: 9 lbs.