Length (A) |
N/A 55 in |
Width (B) |
N/A 66 in |
Height (C) |
N/A 76 in |
Inlet Connection Size |
N/A 2 in |
Outlet Connection Size |
N/A 2 in |
Pump Power |
N/A 10 hp |
Air Flow at 19 inHg1 | N/A 77 scfm |
Tank Capacity |
N/A 120 gal |
Tank Orientation |
N/A Vertical |
Compressor Capacity |
N/A 21,675 Btu/hr |
Sound Level |
N/A 81 dBA |
System Full Load Current (F.L.A) at 208 V |
N/A 54.8 A |
System Full Load Current (F.L.A) at 230 V |
N/A 53.2 A |
System Full Load Current (F.L.A) at 460 V |
N/A 27.6 A |
System Weight |
N/A 2,300 lb |
Electrical Panel Opening |
N/A 42 in |
Minimum Clearance for Ease of Maintenance |
N/A 24 in |
Motor Voltage |
N/A 208 V230 V460 V |
Phase |
N/A 3 |
Power Supply Frequency |
N/A 60 Hz |
N/A
The Powerex enclosed medical vacuum system is designed to create a suction to remove unwanted fluids or gases from hospital working areas. The enclosed medical vacuum system package is compliant with the NFPA 99 requirements for Risk Category 1 systems. Each system is completely tested before shipment and includes: |
N/A
The medical vacuum pumps shall be of the rotary vane air-cooled design. Each vacuum pump shall be direct-driven through a shaft coupling by a TEFC electric motor. Belt drives shall not be permitted. The vacuum pumps shall be mounted on vibration isolators. |
N/A The motor is continuous duty, C-face, TEFC, suitable for 208-230, or 460V, 3 phase, 60 hertz electrical operation. |
N/A The internally lined ASME rated vacuum receiver shall be equipped with a sight gauge, isolation valves, and a manual drain. |
N/A
The control system provides automatic lead/lag sequencing and automatic alternation of all pumps in order to equalize the amount of usage among the available vacuum pumps. The Premium NFPA Control panel shall include a gateway server card and all features listed below: |