- Refrigerant R410A
- Precise temperature control for any industrial application
- Electronic Expansion thermostatic valve
- Separated compressor compartment with removeable panels
- Refrigerant high and low pressure gauges
Unit of Measure
Financing
|
Specifications
|
Dimensions
|
Capacity Ratings
|
Correction Factors (FLEX and TITAN only)
|
Benefits and Advantages
|
Applications
|
Additional Information
Specifications
Brands |
N/A IPC Industrial Process Cooling |
Cooling Capacity |
N/A 75.6 ton907,629 Btu/hr |
Fluid Connections |
N/A 3 inMale Victaulic |
Flow, Nominal |
N/A 180 gpm |
Head Pressure, Nominal |
N/A 40 psi |
Reservoir Capacity |
N/A 132 gal |
Power Supply Voltage |
N/A 460 V |
Power Supply Phase |
N/A 3 |
Power Supply Frequency |
N/A 60 Hz |
Full Load Current |
N/A 257.0 A |
Installed Weight |
N/A 7,061 lb |
Dry Weight |
N/A 6,029 lb |
Refrigerant Type |
N/A R410A |
Capacity Ratings
Fluid Out/In Temperature |
N/A 45 ºF55 ºF |
Ambient Temperature |
N/A 95 ºF |
Minimum Fluid Outlet Temperature |
N/A 41 ºF |
Maximum Fluid Outlet Temperature |
N/A 82 ºF |
Maximum Ambient Temperature |
N/A 113 ºF |
Correction Factors (FLEX and TITAN only)
Correction Factor at 30 Degree Fahrenheit (ºF) Water Outlet Temperature |
N/A 0.68 |
Correction Factor at 35 Degree Fahrenheit (ºF) Water Outlet Temperature |
N/A 0.79 |
Correction Factor at 40 Degree Fahrenheit (ºF) Water Outlet Temperature |
N/A 0.91 |
Correction Factor at 45 Degree Fahrenheit (ºF) Water Outlet Temperature |
N/A 1 |
Correction Factor at 50 Degree Fahrenheit (ºF) Water Outlet Temperature |
N/A 1.09 |
Correction Factor at 55 Degree Fahrenheit (ºF) Water Outlet Temperature |
N/A 1.19 |
Correction Factor at 60 Degree Fahrenheit (ºF) Water Outlet Temperature |
N/A 1.27 |
Correction Factor at 80 Degree Fahrenheit (ºF) Ambient Temperature |
N/A 1.11 |
Correction Factor at 85 Degree Fahrenheit (ºF) Ambient Temperature |
N/A 1.08 |
Correction Factor at 90 Degree Fahrenheit (ºF) Ambient Temperature |
N/A 1.04 |
Correction Factor at 95 Degree Fahrenheit (ºF) Ambient Temperature |
N/A 1 |
Correction Factor at 100 Degree Fahrenheit (ºF) Ambient Temperature |
N/A 0.93 |
Correction Factor at 105 Degree Fahrenheit (ºF) Ambient Temperature |
N/A 0.91 |
Correction Factor at 113 Degree Fahrenheit (ºF) Ambient Temperature |
N/A 0.83 |
Correction Factor at 0 Percent (%) Ethylene Glycol |
N/A 1 |
Correction Factor at 10 Percent (%) Ethylene Glycol |
N/A 0.99 |
Correction Factor at 20 Percent (%) Ethylene Glycol |
N/A 0.98 |
Correction Factor at 30 Percent (%) Ethylene Glycol |
N/A 0.97 |
Correction Factor at 40 Percent (%) Ethylene Glycol |
N/A 0.96 |
Correction Factor at 45 Percent (%) Ethylene Glycol |
N/A 0.95 |
Correction Factor at 50 Percent (%) Ethylene Glycol |
N/A 0.94 |
Benefits and Advantages
Benefits and Advantages |
N/A
Industrial water chillers offer protection to your valuable process equipment - such as spot welders, injection molding equipment, and various other industrial applications. A chiller provides solid protection of your investment twenty-four hours a day, seven day a week during the chiller's lifetime.
|