- Including temperature measurement, optional: pressure measurement
- RS 485 interface, Modbus-RTU as standard
- Integrated display for m³/h and m³
- Applicable from 1/2" to DN 1000
- Easy installation under pressure
- 4...20 mA analog output for m³/h or m³/min
Unit of Measure
Specifications
|
Financing
|
Simple Installation and Removal Under Pressure
|
Options
|
Special Features
Specifications
Ship From Country |
N/A US |
Parameters |
N/A m³/h, CFM (1000 mbar, 20 ºC) in case of compressed air or Nm³/h, Nl/min (1013 mbar, 0 ºC) in case of gases |
Units Adjustable Via Keys at Display |
N/A CFM ft/min g/s kg/h kg/min l/s lb/h lb/min m/s m³/h m³/min |
Adjustable Via Keypad |
N/A Diameter for volume flow calculation, counter resettable |
Sensor |
N/A Thermal Mass Flow Sensor |
Measured Medium |
N/A Air Gases |
Gas Types are Adjustable Over CS Service Software or CS Data Logger |
N/A Air Argon CO2 Nitrogen Oxygen Vacuum |
Accuracy |
N/A ± 0.3% of Full Scale (F.S.) ± 1.5% of Measured Value (M.V.) |
Accuracy on Request |
N/A ± 1.0% of Measured Value (M.V.) ± 0.3% of Full Scale (F.S.) |
Sensor Tube Operating Temperature |
N/A -22 to 230 ºF |
Operating Temperature with Pressure Sensor |
N/A -4 to 185 ºC |
Housing Operating Temperature |
N/A -4 to 158 ºF |
Operating Pressure Range1 | N/A -14.5 to 725 psi |
Digital Output |
N/A Modbus-Remote Terminal Unit (RTU) RS 485 Interface |
Optional Digital Output |
N/A Ethernet Interface M-Bus Power over Ethernet (PoE) |
Analog Output for Cubic Feet Per Minute (CFM) |
N/A 4 to 20 mA |
Pulse Output |
N/A 1 pulse per CF or per liter electrically isolated. Pulse weight can be set on the display. Alternatively, the pulse output can be used as an alarm relay. |
Direct Current (DC) Voltage |
N/A 18 to 36 V |
Power Supply |
N/A 5 W |
Burden |
N/A <500 Ω |
Housing Material |
N/A Polycarbonate |
Housing Protection Standard |
N/A Ingress Protection (IP65) |
Sensor Tube |
N/A Stainless steel, 1.4301, Installation length 8.6 inch, Ø 0.3 Inch |
Mounting Thread |
N/A 1/2" NPT Male Thread |
Housing Diameter |
N/A 2.5 in |
Mounting Position |
N/A Any |
Simple Installation and Removal Under Pressure
Simple Installation and Removal Under Pressure |
N/A
1) Even under pressure, the flow probe VA 500 is mounted by means of a standard 1/2" ball valve. During mounting and dismounting the safety ring avoids an uncontrolled ejection of the probe which may be caused by the operating pressure. For the mounting into different pipe diameters, VA 500 is available in the following probe lengths: 4.72, 6.30, 8.66, 11.81, 15.75 inches, (longer probes available on request). The flow probes are therefore suitable for being mounted into existing pipes with diameters of 1/2" to DN 300 upwards. The exact positioning of the sensor in the middle of the pipe is granted by means of the engraved depth scale. The maximum mounting depth corresponds to the respective probe length. (Probe length 8.66 inch = 220 mm maximum mounting depth). 2) If there is no suitable measuring site with 1/2" ball valve, there are two easy ways to set up a measuring site: A Weld on a 1/2" screw neck and screw on a 1/2" ball valve B Mount spot drilling collar incl. ball valve. By means of the drilling jig, it is possible to drill under pressure through the 1/2" ball valve into the existing pipe. The drilling chips are collected in a filter. Then install the probe as described under 1). 3) Due to the large measuring range of the probe even extreme requirements to the consumption measurement (high volume flow in small pipe diameters) can be met. The measuring range is depending on the pipe diameter. |
- 1 For pressure > 145 psi - order additional high-pressureprotection