Specifications
Housing |
N/A 9.80 x 13.74 x 4.29 in |
Housing Material |
N/A Powder-Coated Aluminum, Polyester Front Faceplate |
Housing Protection Standard |
N/A IP65 |
Connections |
N/A 16 x M12 x 1.5 nickel-plated brass for sensor and supply, alarm relay, 1 x RJ 45 Ethernet connection |
Sensor Inputs |
N/A 4/8/12 sensor input for analog and digital sensors can be freely connected Analog remote sensors 0/4-20 mA, 0-1/10/30 V, pulse, Pt 100/Pt 1000, KTY Analog sensors for pressure, temperature, current probe preconfigured Digital sensors for dew point and consumption with SDI interface FLM/DPM series RS 485/Modbus RTU digital remote sensors, other bus systems are possible on request |
Data Logging |
N/A Infinite and fully customizable |
Power Supply for Sensors |
N/A 24 VDC, maximum 130 mA per sensor, integrated power supply unit maximum 24 VDC, 25 W In version 8/12 sensor inputs 2 integrated power supply units each maximum 24 VDC, 25 W |
Interface Type |
N/A Ethernet/RS 485 Modbus RTU/TCP Integrated web server (optional) SDI other bus systems on request USB cable USB stick |
Output |
N/A 3/4 relay (changeover contact 230 VAC, 6 A) alarm management, relay freely programmable, summary alarm Analog output, pulse at sensor with its own signal output looped through, e.g. DPM/FLM series |
Memory Card |
N/A Memory size 2 GB SD memory card standard, optional up to 4 GB |
Display Type |
N/A Full color, 7 in. TFT touchpanel transmissive, graphics, charts, statistics |
Operating Temperature |
N/A 33 to 122 ºF |
Storage Temperature |
N/A -4 to 158 ºF |
Warranty |
N/A 5 years |
Standard Features and Benefits
N/A
High Measurement Accuracy: |