FA 500 is the ideal dew point measuring instrument with integrated display and alarm relay for refrigeration, membrane and adsorption dryers.
Unit of Measure

Financing

Approve Payments

N/A Finance with Approve Payments

Specifications

Measuring Range (Atmospheric Pressure)

N/A -4 to 122 ºF

Relative Humidity

N/A 100 %

Accuracy (±) at 122 to -4 Degree Fahrenheit (ºF) Temperature

N/A 1.8 ºF

Accuracy (±) at -4 to -58 Degree Fahrenheit (ºF) Temperature (Atmospheric Pressure)

N/A 3.6 ºF

Accuracy (±) at -58 to -112 Degree Fahrenheit (ºF) Temperature (Atmospheric Pressure)

N/A 5.4 ºF

Pressure Range

N/A -1 to 50 bar

Pressure Range (Special Version)

N/A 7251 psi

Direct Current (DC) Voltage

N/A 10 to 36 V24 V

Protection Class

N/A IP 65

Electromagnetic Compatibility (EMC)

N/A In According with DIN EN 61326-1

Operating Temperature

N/A -4 to 122 ºF

Connection

N/A 2 x M12, 5-pin for analog output, Modbus-RTU and alarm output, M-Bus (optional) Ethernet (PoE) (optional)

Personal Computer (PC) Connection

N/A Modbus-RTU interface (RS 485)

Analog Output

N/A 4 to 20 mA = -112 to 68 °Ftd 4 to 20 mA = -4 to 122 °Ftd 4 to 20 mA = -76 to 86 °Ftd

Burden for Analog Output

N/A < 500 Ω

Alarm Relay

N/A NC, max. 60 VDC, 0.5 A

Screw-In Thread

N/A G 1/2 in.

Dimensions

Width

N/A 3.01 in

Depth

N/A 3.35 in

Height

N/A 2.95 in

Special Features

Special Features

N/A
  • Integrated display
  • Threshold value adjustable via keypad, alarm relay (max. 60 VDC, 0.5 A)
  • Pressure-tight up to 7251 psi (special version)
  • Extremely stable in the long term
  • Quick adaption time
  • 4...20 mA analog output for dew point
  • Different refrigeration and adsorption dryer versions
  • NEW: Modbus-RTU interface
  • NEW: Higher resolution of sensor signal due to the improved evaluation electronics
  • NEW: Sensor diagnosis on site with a portable device or CS Service Software

Readable via Modbus

Readable via Modbus

N/A
  • Pressure dew point [ºFtd]
  • Temperature [ºF]
  • rel. humidity [% RH]
  • abs. humidity [g/m³]
  • Degree of humidity [g/kg]
  • Moisture content V/V [ppmV/V]
  • Partial vapor pressure [hPa]
  • Atmospheric dew point [ºFtd.atm]

Easy Operation Via Keys on Display

Easy Operation Via Keys on Display

N/A The integrated display shows the dew point in big figures as well as further humidity parameters on two more display pages. The arrow key can be used to scroll between the display pages.

The alarm threshold value for the integrated relay can be freely entered via the keys. In addition to the alarm threshold, the hysteresis can also be freely entered.

The 4 to 20 mA analog output can be scaled freely or also allocated to one further parameter, e. g. g/m³.

After entering the system pressure of the compressed air system and the reference pressure (atmospheric pressure), the sensor can also calculate back to the atmospheric dew point from the measured pressure dew point if desired.

Options

Options

N/A item-74026
item-74027
item-74028
item-74012
item-74013
item-74014
item-74015
item-74016