Maximum Working Temperature
|
|
250 ºF
|
|
|
|
|
- Complete Package includes aftercooler/oil cooler, fan, motor, guards and mounting brackets.
- Convert Water cooled compressors to air cooled. Eliminate corrosion and expensive water bills.
- Remote Mount the cooling package from the compressor to reduce noise, or to a cleaner, cooler, more convenient location.
- Canadian Registry Numbers Available
|
|
|
|
Oil Cooler = Compressor Horsepower x 1.15 (motor service factor) x 0.83 (this assumes 83% of input horsepower is rejected to heat) Aftercooler = Compressor Horsepower x 1.15 (motor service factor) x 0.17 (this assumes 17% of input horsepower is rejected to heat)
|
|
|
|
- Electric motors are totally enclosed, and are not thermally protected.
- Actual ratings vary with motor brand. Check motor nameplate for actual ratings.
- Motor RPM is reduced by 1/6 for 50 Hz service.
|
|
|